Figure 151:
Voltage dependent inverse time characteristics for underfrequency
protection SAPTUF. The time delay to operate is plotted as a
function of the measured voltage, for the Exponent = 0, 1, 2, 3, 4
respectively.
9.1.6.4
Blocking
M13354-50 v7
It is possible to block underfrequency protection SAPTUF partially or completely,
by binary input signals or by parameter settings, where:
BLOCK:
blocks the START, TRIP and
RESTORE outputs
BLKTRIP:
blocks the TRIP output
BLKREST:
blocks the RESTORE output
If the measured voltage level decreases below the setting of
IntBlockLevel
, both the
START and the TRIP outputs are blocked.
9.1.6.5
Design
M13354-63 v10
The frequency measuring element continuously measures the frequency of the
positive sequence voltage and compares it to the setting
StartFrequency
. The
frequency signal is filtered to avoid transients due to switchings and faults. The
time integrator can operate either due to a definite delay time or to the special
voltage dependent delay time. When the frequency has returned back to the setting
of
RestoreFreq
, the RESTORE output is issued after the time delay
tRestore
. The
design of underfrequency protection SAPTUF is schematically described in
figure
1MRK 506 382-UEN A
Section 9
Frequency protection
Line distance protection REL650 2.2 IEC
303
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...