Figure 132:
Example for Definite Time Delay stage1 operation
8.1.7.3
Blocking
M15326-20 v8
It is possible to block Two step undervoltage protection UV2PTUV partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:
blocks all outputs
BLKTR1:
blocks all trip outputs of step 1
BLKST1:
blocks all start and trip outputs related to step 1
BLKTR2:
blocks all trip outputs of step 2
BLKST2:
blocks all start and trip outputs related to step 2
If the measured voltage level decreases below the setting of
IntBlkStVal1
, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the
IntBlkSel1
parameter. This internal
blocking can also be set to
Off
resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure
. The delay of the blocking function must
be set less than the time delay of under voltage function.
Section 8
1MRK 506 382-UEN A
Voltage protection
270
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...