The inner resistive characteristic in the third quadrant outside the load
encroachment zone consist of the sum of the settings
R1FInRv
and the line
resistance
R1LIn
. The argument of the tilted lines outside the load encroachment is
the same as the tilted lines in the first quadrant. The distance between the inner and
outer boundary is the same as for the load encroachment in reverse direction, that is
D
Rv.
6.2.6.3
Reactive reach in forward and reverse direction
M13877-20 v3
The inner characteristic for the reactive reach in forward direction correspond to
the setting parameter
X1InFw
and the outer boundary is defined as
X1InFw
+
D
Fw,
where:
D
Fw =
RLdOutFw - KLdRFw · RLdOutFw
The inner characteristic for the reactive reach in reverse direction correspond to the
setting parameter
X1InRv
for the inner boundary and the outer boundary is defined
as
X1InRv
+
D
Rv.
where:
D
Rv =
RLdOutRv - KLdRRv · RLdOutRv
6.2.6.4
Basic detection logic
M13877-24 v7
The operation of the Power swing detection ZMRPSB is only released if the
magnitude of the current is above the setting of the min operating current,
IMinOpPE
.
ZMRPSB function can operate in two operating modes:
•
The
1 out of 3
operating mode is based on detection of power swing in any of
the three phases. Figure
presents a composition of an internal detection
signal DET-L1 in this particular phase.
•
The
2 out of 3
operating mode is based on detection of power swing in at least
two out of three phases. Figure
presents a composition of the detection
signals DET1of3 and DET2of3.
Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure
are
related to the operation of the impedance measuring elements in each phase
separately (
n
represents the corresponding L1, L2 and L3). They are internal
signals, calculated by ZMRPSB function.
The
tP1
timer in figure
serve as detection of initial power swings, which are
usually not as fast as the later swings are. The
tP2
timer become activated for the
detection of the consecutive swings, if the measured impedance exit the operate
area and returns within the time delay, set on the
tW
waiting timer. The upper part
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
127
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...