Complete configuration description of all IEDs in a station and the full engineering
of process signals and communication structure is included. This includes all needed
data sets and all control blocks.
•
CID = Configured IED Description
•
The CID file contains the information needed to configure just one specific IED.
The uploading of IEC 61850 communication configuration is not supported
when reading a configuration from an online IED.
7.2
IEC 61850 engineering procedure
7.2.1
IEC 61850 protocol references and pre-conditions
SEMOD58549-4 v3
To engineer the IEC 61850 protocol interface for the IED, the following additional manuals or
knowledge of their contents is required.
•
Knowledge of the IEC 61850 engineering process as described in the IEC 61850 standard.
•
The Technical Manual describes function blocks defined as logical nodes.
•
The IEC 61850 Communication Protocol Manual.
•
The IEC 61850 conformance documents for the IED to be engineered.
7.2.2
Sequence for engineering of IEC 61850 protocol
SEMOD58549-17 v6
The IEC 61850 standard defines the complete part needed for information communication in a
substation. This can be split into the following parts:
•
Description of the substation part including the used logical nodes
•
Description of the IEDs with their logical nodes
•
Description of the communication network
•
Description of the engineering process
For more details please refer to the IEC 61850 standards. In the following description it is
assumed that PCM600 together with IET600 is used as system configuration tool.
A short form of a typical sequence is shown in
when a complete station is exported
as a SCD file.
1.
Export SCL files from PCM600. In the scenario in
it is a SCD file. Other SCL file
types are possible to export.
2.
Configure horizontal and vertical communication in the IET600 station configuration tool.
3.
Import SCL files to PCM600 project. In the scenario in
it is the updated SCD file.
Section 7
1MRK 511 284-UEN B
IEC 61850 communication engineering
78
650 series
Engineering manual
© Copyright 2013 ABB. All rights reserved