Evaluation of the results from the disturbance recording function requires access to a PC
either permanently connected to the IED or temporarily connected to the Ethernet port (RJ-45)
on the front. The PCM600 software package must be installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party tool with IEC
61850 protocol. Reports can automatically be generated from PCM600. Disturbance files can
be analyzed by any tool reading Comtrade formatted disturbance files.
It could be useful to have a printer for hard copies. The correct start criteria and behavior of
the disturbance recording function can be checked when IED protective functions are tested.
When the IED is brought into normal service it is recommended to delete all recordings, made
during commissioning to avoid confusion in future fault analysis.
All recordings in the IED can be deleted in two ways:
1.
in the local HMI under Main menu/Clear/Reset disturbances, or
2.
in the Disturbance handling tool in PCM600 by selecting
Delete all recordings in the IED...
in the window
Available Recordings in IED.
9.1.4
Event recorder (ER) and Event list (EL)
M12645-2 v7
The result from the event recorder and event list can be viewed on the local HMI or, after
upload, in PCM600 as follows:
1.
on the local HMI under Main menu/Events, or in more details via
2.
the
Event Viewer in PCM600.
The internal FIFO register of all events will appear when the event viewer is launched.
When the IED is brought into normal service it is recommended to delete all events resulting
from commissioning tests to avoid confusion in future fault analysis. All events in the IED can
be cleared in the local HMI under Main Menu//Clear/Clear internal event list or Main menu/
Clear/Clear process event list. It is not possible to clear the event lists from PCM600.
When testing binary inputs, the event list (EL) might be used instead. No uploading or
analyzing of registrations is then needed since the event list keeps running, independent of
start of disturbance registration.
9.2
Identifying the function to test in the technical
reference manual
M11748-2 v4
Use the technical manual to identify function blocks, logic diagrams, input and output signals,
setting parameters and technical data.
9.3
Current protection
SEMOD53531-1 v1
9.3.1
Instantaneous phase overcurrent protection 3-phase output
PHPIOC
M11754-3 v8
Prepare the IED for verification of settings outlined in Section
.
Section 9
1MRK 505 385-UEN C
Testing functionality by secondary injection
60
Breaker protection REQ650
Commissioning manual