IEC15000025 V1 EN-US
5.
Select and edit the values.
6.
Click
Acknowledge and send.
IEC15000026 V1 EN-US
This commits the values to the IED and exits the editing session.
7.
Click
Cancel to abort the changes and revert back to actual IED values.
IEC15000032 V1 EN-US
Regardless if the forcing changes are commited or canceled, the forcing is still
active.
To force more signals, click the button
Start editing signal value for forcing again.
8.8.4
How to undo forcing changes and return the IED to normal
operation
GUID-00E2BAD8-A29E-4B9D-80E6-E12F59E019BD v1
Regardless of which input/output signals have been forced, all forced signals will return to
their normal states immediately when the IED is taken out of test mode.
When the forcing is removed by exiting from IED test mode, both input and
output signals may change values. This means that logic input signals may
activate functions in the IED and that output relays may change state, which
can be potentially dangerous.
Section 8
1MRK 505 385-UEN C
Testing IED operation
56
Breaker protection REQ650
Commissioning manual