8.2.3
Additional indications
The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data
is found under the IED status and in the internal event list.
Table 16:
Additional indications
Warning indication
Additional information
Time Synch Error
Source of the time synchronization is lost or time
system has made a time reset.
BATTERY1 Error
Auxiliary power is disconnected.
Settings Changed
Settings have been changed.
Setting Groups Changed
Setting group has been changed.
8.3
Correction procedures
8.3.1
Changing and setting the password
The password can only be set with PCM600.
For more information, see PCM600 documentation.
8.3.2
Identifying IED application problems
Navigate to the appropriate menu in the LHMI to identify possible problems.
•
Check that the function is on.
•
Check that the correct setting group (1 to 4) is activated.
•
Check the blocking.
•
Check the mode.
•
Check the measurement value.
•
Check the connection to trip and DFR functions.
•
Check the channel settings.
1MRK 506 331-UUS A
Section 8
Troubleshooting
153