Table 14:
Internal fault indications
Fault indication
Additional information
Internal Fault
Real Time Clock Error
Hardware error with the real time clock.
Internal Fault
Runtime Exec. Error
One or more of the application threads
are not working properly.
Internal Fault
SW Watchdog Error
This signal will be activated when the
terminal has been under too heavy
load for at least 5 minutes.
Internal Fault
Runtime App Error
One or more of the application threads
are not in an expected state.
Internal Fault
File System Error
A file system error has occurred.
Internal Fault
TRM-Error
A TRM card error has occurred. The
instance number is displayed at the
end of the fault indication.
Internal Fault
COM-Error
A COM card error has occurred. The
instance number is displayed at the
end of the fault indication.
Internal Fault
PSM-Error
A PSM card error has occurred. The
instance number is displayed at the
end of the fault indication.
8.2.2
Warnings
The warning message associated with the fault is found in the internal event list in the
LHMI menu
Main menu/Diagnostics/Internal events
. The message includes the date,
time, description and signal state for the fault. The current status of the internal fault
signals can also be checked via the LHMI in
Main menu/Diagnostics/IED status/
General
.
When a fault appears, record the fault indication message and state it when ordering
service.
Table 15:
Warning indications
Warning indication
Additional information
Warning
IEC 61850 Error
IEC 61850 has not succeeded
in some actions such as
reading the configuration file,
startup etc.
Warning
DNP3 Error
Error in DNP3 communication.
Section 8
1MRK 506 331-UUS A
Troubleshooting
152
Commissioning Manual
Summary of Contents for Relion 650 Series REL650
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Commissioning Manual ...
Page 2: ......
Page 8: ......
Page 22: ...14 ...
Page 44: ...36 ...
Page 52: ...44 ...
Page 156: ...148 ...
Page 166: ...158 ...
Page 175: ...167 ...