![ABB Relion 650 1.1 IEC Installation Manual Download Page 25](http://html1.mh-extra.com/html/abb/relion-650-1-1-iec/relion-650-1-1-iec_installation-manual_4693087025.webp)
A
B
C
GUID-F360FEBB-FE45-4305-81C8-3E7A7CF117B1 V1 EN-US
Figure 3:
Flush mounted IED
A 222 mm + 12 mm with ring-lug connector
B 27 mm
C 13 mm
Check the allowed minimum bending radius from the optical cable
manufacturer.
5.3.2
Rack mounting the IED
5.3.2.1
Rack mounting a single IED
GUID-E5E49AF2-DD48-43BA-9B1B-5FA92CED1DAC v2
1.
Remove the four plastic plugs from the right-hand side of the IED and attach the right
mounting panel securely using the required screws.
2.
Tighten the screws.
1MRK 514 014-UEN A
Section 5
Mounting
650 series
19
Installation manual