3.14.2.3
Settings
Setting tables for A1RADR and A2RADR are similar except for channel numbers.
•
A1RADR, channel01 - channel10
•
A2RADR, channel11 - channel20
Table 51:
A1RADR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation Ch 1
Off
On
-
-
Off
Operation On/Off
Table 52:
A1RADR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Nominal value Ch 1
0.0 - 999999.9
-
0.1
0.0
Nominal value for
analog channel 1
Under trigger Ch 1
Off
On
-
-
Off
Use under level
trigger for analog
channel 1 (on) or not
(off)
Under Trg Lev Ch 1
0 - 200
%
1
50
Under trigger level
for analog channel 1
in % of signal
Over trigger Ch 1
Off
On
-
-
Off
Use over level
trigger for analog
channel 1 (on) or not
(off)
Over Trg Lev Ch 1
0 - 5000
%
1
200
Over trigger level for
analog channel 1 in
% of signal
IEC60870-5-103
Function type Ch 1
0 - 255
-
1
0
Function type for
analog channel 1
(IEC60870-5-103)
Information Num Ch
1
0 - 255
-
1
0
Information number
for analog channel 1
(IEC60870-5-103)
Settings are the same for each channel. The channel numbers are
shown after the parameter name in LHMI and PCM600.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
87
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...