This module inhibits the
OC_STR
and
OC_OPR
outputs and slow load-shedding
trigger due to external input in any of the following conditions.
•
The input
INHIBIT_TRG
is TRUE.
•
The input
SLS_DISABLE
is TRUE.
•
The load-shedding blocking status (from the Block logic module) is TRUE.
If the Over current based load shed module is disabled, the outputs
OC_OPR
and
OC_STR
are FALSE, the Slow load shed trigger module due to external input
EXT_OC_SLST
is inactive and the outputs
OC_TIME
and
ELAPSE_TIME
are zero.
The Over current based load shed module provides the
OC_STR
(overcurrent start)
signal to the Slow load shed logic module. It also provides the
OC_OPR
(overcurrent
operate), external slow load-shedding trigger signal to the Slow load shed logic
module and the Binary to integer module.
7.4.4.7
Demand based load shed
This module calculates the linear average demand based on an active power (from the
Power monitoring module) of the power source over a set interval time. Based on the
comparison of the linear average demand and set maximum demand value of source,
demand-based slow load-shedding action is initiated.
The
Slow load shed mode
setting enables or disables the Demand based load shed
module. If the
Slow load shed mode
setting is "Max Dmd Trg" or "OC, Max Dmd, Ext
Trg", the Demand based load shed is enabled, else it is disabled
Based on the measured powers (power received from source IED), the Demand based
load shed module internally calculates the linear average of the demand over the
Demand interval
setting. The
Demand interval
setting can be set to "1 Minute", "5
Minute", "10 Minute", "15 Minute", "30 Minute", "60 Minute" or "180 Minute". A
new demand value is obtained every one minute, indicating the actual demand over
the time interval preceding the update time. Based on the sliding average and final
output value, the demand values are updated at the end of the time interval. For
monitoring, the demand value output is
AVG_DEMAND
in kilowatt and the energy
demand output is
PERIODIC_KWH
in kilowatt hour.
For example, the demand value based on the setting interval "180 Minute" is displayed
in the output for the first time after 180 minutes and the value is calculated from the
interval t0 – t180. The next value is displayed at the t180+1 and it is based on the
average between t0+1 – t180+1.
If the linear average of the demand on the power source exceeds the
Maximum demand
setting limit, the
MAX_DMD_ALM
output (maximum demand operate) is TRUE. The
RESET_DEMAND
input resets the Demand based load-shedding module. If the
RESET_DEMAND
input is TRUE, the
MAX_DMD_ALM
output is TRUE and both the
AVG_DEMAND
and
PERIODIC_KWH
outputs are reset to zero.
Section 7
1MRS757256 F
Power management functions
224
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...