Load-shedding blocking = TRUE
t
T
0
T
2
T
3
T
4
T
5
T
Load-shedding blocking = FALSE
GUID-AC44FCB5-C8E0-4CF2-9608-CB82879B1244 V1 EN
Figure 132:
Logic for load-shedding blocking status at the time of measurement
cycle
q
=
Bad
q
=
Good
Load-shedding blocking = FALSE
0
T
2
T
3
T
4
T
5
T
Load-shedding blocking = TRUE
GUID-82D266F7-DA92-4661-B1BA-8AC28635BD1F V1 EN
Figure 133:
Logic for load-shedding blocking status within the measurement
cycle
Where
q
CB_IED_QVAL
T, 2T, 3T
Measurement cycle
t
Time between the change of CB_IED_QVAL input from “Bad” to “Good” and the next
measurement cycle.
If the
IED_TST_MODE
input is TRUE or the
CB_POSITION
input is "Invalid”, or
the
CB_POSITION
input remains in the “Intermediate” position for more than the
CB
Interm time
setting, the load-shedding blocking status is TRUE.
The load-shedding blocking status is reported to the General logic module, Fast load-
shedding trigger logic module, Slow load-shedding logic module, Over current based
load-shedding module and Demand based load-shedding module.