The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the binary single point values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.
3.27.4
Signals
Table 103:
GOOSESPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 104:
GOOSESPRCV Output signals
Name
Type
Description
SPOUT
BOOLEAN
Single point output
DATAVALID
BOOLEAN
Data valid for single point output
COMMVALID
BOOLEAN
Communication valid for single point output
TEST
BOOLEAN
Test output
3.27.5
Settings
Table 105:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
133
Technical Manual