Section 3
Logical node extensions
3.1
New logical nodes
Table 3:
New functions in PML630
LN Class
Prefix
LN Type
Description
ACLS
LSC
LSCACLS
LN Class: 'A' for Automatic control, 'C' for Contingency
based, 'LS' for Load shedding)
LN Prefix: Contingency based Load shedding (Fast load
shedding)
ACLS
PWS
PWSACLS
LN Class: 'A' for Automatic control, 'C' for Contingency
based, 'LS' for Load shedding)
LN Prefix: PoWer Source (Slow load shedding for Grid
Transformers)
CCLS
LSC
LSCCCLS
LN Class: 'C' for Supervisory control, 'C' for Contingency
based, 'LS' for Load shedding)
LN Prefix: Load shedding (Manual) Control
RCLS
SNWL
SNWLRCLS
LN Class: 'R' for (Load shedding) Related (function), 'C'
for Contingency based, 'LS' for Load shedding)
LN Prefix: SubNetWork Load shed information
RCLS
SNWA
SNWARCLS
LN Class: 'R' for (Load shedding) Related (function), 'C'
for Contingency based, 'LS' for Load shedding)
LN Prefix: SubNetWork Accumulated load power
information
RCLS
LSC
LSCRCLS
LN Class: 'R' for (Load shedding) Related (function), 'C'
for Contingency based, 'LS' for Load shedding)
LN Prefix: (Substation) Load shedding controller
information summary
3.1.1
LSCACLS
Table 4:
LSCACLS
Attribute name
DATA type
Explanation
M/O/E
ACLS class
ACLS
Contingency load shedding (Fast LS)
M
Data
Common logical node information
Mod
ABB_c_dINC
Mode (load shed function Enable /
Disable / Test command/status)
M
Beh
ABB_a_dINS
Behaviour (reflects the mode of the
function)
M
Health
ABB_c_dINS
Health
M
NamPlt
ABB_b_dLPL
Name plate
M
Table continues on next page
1MRS757261 E
Section 3
Logical node extensions
PML630/Compact Load-Shedding Solution
11
Point List Manual