The inputs from the protection functions are connected to the
OPERATE
input.
Usually, a logic block OR is required to combine the different function outputs to
this input. The
TRIP
output is connected to the binary outputs on the IO board. This
signal can also be used for other purposes within the protection relay, for example
when starting the breaker failure protection.
TRPPTRC is used for simple three-phase tripping applications.
BI#4
Lock-out
reset
OR
PO#1
BI#2
TRPPTRC
OPERATE
RST_LKOUT
TRIP
CCRBRF-trret
T1PTTR-operate
CBXCBR-open
PHLPTOC-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC-operate
NSPTOC1-operate
NSPTOC2-operate
EFLPTOC1-operate
EFHPTOC-operate
EFIPTOC-operate
PDNSPTOC-operate
EFLPTOC2-operate
ARCPSARC1-operate
ARCPSARC2-operate
ARCPSARC3-operate
DARREC-open cb
BLOCK
CL_LKOUT
Figure 430: Typical TRPPTRC connection
5.3.6
Signals
Table 783: TRPPTRC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block of function
OPERATE
BOOLEAN
0=False
Operate
RST_LKOUT
BOOLEAN
0=False
Input for resetting the circuit break-
er lockout function
Table 784: TRPPTRC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip output signal
CL_LKOUT
BOOLEAN
Circuit breaker lockout output (set
until reset)
Protection related functions
1MRS757644 H
818
620 series
Technical Manual