4.11.7
Settings
Table 733: MAPGAPC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
–10000.0...10000.0
0.1
0.0
Start value
Start value Add
–100.0...100.0
0.1
0.0
Start value Add
Operate delay time 0...200000
ms
100
0
Operate delay time
Table 734: MAPGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Over
2=Under
1=Over
Operation mode
Table 735: MAPGAPC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
100
0
Reset delay time
Absolute hysteresis 0.01...100.00
0.01
0.10
Absolute hysteresis
for operation
4.11.8
Monitored data
Table 736: MAPGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
MAPGAPC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.11.9
Technical data
Table 737: MAPGAPC Technical data
Characteristic
Value
Operation accuracy
±1.0 % of the set value or ±20 ms
4.12
Capacitor bank protection
Protection functions
1MRS757644 H
772
620 series
Technical Manual