Table 715: ARCSARC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
ARC_FLT_DET
BOOLEAN
Fault arc detected=light sig-
nal output
4.9.7
Settings
Table 716: ARCSARC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase start value
0.50...40.00
xIn
0.01
2.50
Operating phase
current
Ground start value
0.05...8.00
xIn
0.01
0.20
Operating residual
current
Operation mode
1=Light+current
2=Light only
3=BI controlled
1=Light+current
Operation mode
Table 717: ARCSARC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
4.9.8
Monitored data
Table 718: ARCSARC Monitored data
Name
Type
Values (Range)
Unit
Description
ARCSARC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.9.9
Technical data
Table 719: ARCSARC Technical data
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 × I
n
Operate time
Minimum
Typical
Maximum
Table continues on the next page
Protection functions
1MRS757644 H
756
620 series
Technical Manual