4.1.7.9
Technical data
Table 340: T2PTTR Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2
Hz
Current measurement: ±1.5% of the set value or ±0.002 x I
n
(at currents in the range of 0.01...4.00 x I
n
)
Operate time accuracy
±2.0% of the theoretical value or ±0.50 s
4.1.7.10
Technical revision history
Table 341: T2PTTR Technical revision history
Technical revision
Change
B
Added the
AMB_TEMP
input
C
Internal improvement.
D
Internal improvement.
4.1.8
Motor load jam protection JAMPTOC
4.1.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Motor load jam protection
JAMPTOC
Ist>
51LR
4.1.8.2
Function block
Figure 173: Function block
4.1.8.3
Functionality
The motor load jam protection function JAMPTOC is used for protecting the motor
in stall or mechanical jam situations during the running state.
When the motor is started, a separate function is used for the startup protection,
and JAMPTOC is normally blocked during the startup period. When the motor has
1
Overload current > 1.2 x Operate level temperature
1MRS757644 H
Protection functions
620 series
Technical Manual