3.20.1.3
Signals
Table 211: RCHLCCH output signals
Parameter
Values
(Range)
Unit
Step
Defaul
t
Description
CHLIV
True
False
Status of redundant Ethernet chan-
nel LAN A. When
Redundant mode
is set to "HSR" or "PRP", value is
"True" if the protection relay is
receiving redundancy supervision
frames. Otherwise value is "False".
REDCHLIV
True
False
Status of redundant Ethernet chan-
nel LAN B. When
Redundant mode
is set to "HSR" or "PRP", value is
"True" if the protection relay is
receiving redundancy supervision
frames. Otherwise value is "False".
LNKLIV
Up
Down
Link status of redundant port LAN
A. Valid only when
Redundant mode
is set to "HSR" or "PRP".
REDLNKLIV
Up
Down
Link status of redundant port LAN
B. Valid only when
Redundant mode
is set to "HSR" or "PRP".
3.20.1.4
Settings
Table 212: Redundancy settings
Parameter
Values
(Range)
Unit
Step
Defaul
t
Description
Redundant
mode
None
PRP
HSR
None
Mode selection for Ethernet switch
on redundant communication mod-
ules. The "None" mode is used with
normal and Self-healing Ethernet
topologies.
3.20.1.5
Monitored data
Monitored data is available in four locations.
• Monitoring > Communication > Ethernet > Activity > CHLIV_A
• Monitoring > Communication/ > Ethernet > Activity > REDCHLIV_B
• Monitoring > Communication > Ethernet > Link statuses > LNKLIV_A
• Monitoring > Communication > Ethernet > Link statuses > REDLNKLIV_B
3.20.2
Ethernet channel supervision SCHLCCH
Basic functions
1MRS757644 H
236