Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
-1=Off
Operation mode for generic con-
trol point
Pulse length
10...3600000
ms
10
1000
Pulse length for pulsed operation
mode
Description
SPCGAPC1 Output 16 Generic control point description
3.17.12
Remote generic control points SPCRGAPC
3.17.12.1
Function block
Figure 109: Function block
3.17.12.2
Functionality
The remote generic control points function SPCRGAPC is dedicated only for remote
controlling, that is, SPCRGAPC cannot be controlled locally. The remote control is
provided through communications.
3.17.12.3
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
SPCRGAPC has the
Operation mode, Pulse length and Description settings available
to control all 16 outputs. By default, the
Operation mode setting is set to "Off". This
disables the controllable signal output. SPCRGAPC also has a general setting
Loc
Rem restriction, which enables or disables the local or remote state functionality.
When the
Operation mode is set to "Toggle", the corresponding output toggles
between "True" and "False" for every input pulse received. The state of the output is
stored in a nonvolatile memory and restored if the protection relay is restarted.
When the
Operation mode is set to "Pulsed", the corresponding output can be used
to produce the predefined length of pulses. Once activated, the output remains
active for the duration of the set pulse length. When activated, the additional
activation command does not extend the length of pulse. Thus, the pulse needs
to be ended before the new activation can occur.