The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
3.15.5.3
Signals
Table 75: GOOSERCV_INTL Output signals
Name
Type
Description
POS_OP
BOOLEAN
Position open output signal
POS_CL
BOOLEAN
Position closed output signal
POS_OK
BOOLEAN
Position OK output signal
VALID
BOOLEAN
Output signal
3.15.6
GOOSERCV_CMV function block
3.15.6.1
Function block
Figure 61: Function block
3.15.6.2
Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to
the application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in
the GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application.
Default value (0) is used if VALID output indicates invalid status.
3.15.6.3
Signals
Table 76: GOOSERCV_CMV Output signals
Name
Type
Description
MAG
FLOAT32
Output signal (amplitude)
ANG
FLOAT32
Output signal (angle)
VALID
BOOLEAN
Output signal
1MRS757644 H
Basic functions
620 series
Technical Manual
143