![ABB Relion 620 Series Manual Download Page 13](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_manual_3414585013.webp)
1MAC302441-MB A
Section 1
Introduction
RER620
7
Point List Manual
1.4.3
Functions, codes and symbols
Table 1:
RER620 functions, codes and symbols
Function
IEC61850
IEC60617
ANSI/C37.2
Current Protection
Single-phase non-directional time overcurrent protection with 1-ph trip option, low stage
SPHLPTOC1
3I>(1)
51P
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 1
SPHLPTOC2
3I>(2)
50P-1
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 2
SPHHPTOC1
3I>>(1)
50P-2
Single-phase non-directional instantaneous overcurrent protection with 1-ph trip option
SPHIPTOC1
3I>>>(1)
50P-3
Non-directional time overcurrent ground-fault protection, low stage
XEFLPTOC2
Io>(2)
51N
Non-directional time overcurrent ground-fault protection, high stage 1
XEFLPTOC3
Io>(3)
50N-1
Non-directional time overcurrent ground-fault protection, high stage 2
XEFHPTOC3
Io>>(3)
50N-2
Non-directional instantaneous time overcurrent ground-fault protection
XEFIPTOC2
Io>>>(2)
50N-3
Non-directional sensitive earth-fault
EFLPTOC3
Io>(3)
50SEF
Negative sequence non-directional time overcurrent protection 1
XNSPTOC1
I2 >(1)
46-1
Negative sequence non-directional time overcurrent protection 2
XNSPTOC2
I2 >(2)
46-2
Phase discontinuity protection
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INPHAR
3I2f >
INR
Directional Protection
Single-phase directional overcurrent protection, low stage 1
SDPHLPDOC1
3I >->(1)
67/51P-1
Single-phase directional overcurrent protection, low stage 2
SDPHLPDOC2
3I >->(2)
67/51P-2
Directional ground-fault protection, low stage 1
XDEFLPDEF1
Io>->(1)
67/51N-1
Directional ground-fault protection, low stage 2
XDEFLPDEF2
Io>->(1)
67/51N-2
Cold Load Timers
Cold load timer 1 Phase A (in seconds)
TPSGAPC1
TPS(1)
62CLD-1
Cold load timer 2 Phase A (in minutes)
TPMGAPC1
TPM(1)
62CLD-2
Cold load timer 1 Phase B (in seconds)
TPSGAPC2
TPS(2)
62CLD-3
Cold load timer 2 Phase B (in minutes)
TPMGAPC2
TPM(2)
62CLD-4
Cold load timer 1 Phase C (in seconds)
TPSGAPC3
TPS(3)
62CLD-5
Cold load timer 2 Phase C (in minutes)
TPMGAPC3
TPM(3)
62CLD-6
Voltage Protection
Three-phase overvoltage 1, source 1 low stage
PHPTOV1
3U >(1)
59-1
Three-phase overvoltage 2, source 1 high stage
PHPTOV2
3U >(2)
59-2
Three-phase overvoltage 3, source 2 low stage
PHPTOV3
3U >(3)
59-3
Three-phase undervoltage 1, source 1 low stage
PHPTUV1
3U <(1)
27-1
Three-phase undervoltage 2, source 1 high stage
PHPTUV2
3U <(2)
27-2
Three-phase undervoltage 3, source 2 low stage
PHPTUV3
3U <(3)
27-3
Positive sequence overvoltage protection, source1
PSPTOV1
U1>(1)
59PS-1
Positive sequence overvoltage protection, source 2
PSPTOV2
U1>(2)
59PS-2
Negative sequence overvoltage protection, source1
NSPTOV1
U2>(1)
47
Negative sequence overvoltage protection, source 2
NSPTOV2
U2>(2)
47-2
Zero sequence overvoltage protection, source1
ROVPTOV1
Uo>(1)
59N-1
Summary of Contents for Relion 620 Series
Page 2: ......
Page 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Page 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Page 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Page 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...