4.6.1.9
Technical data
Table 594:
81 Technical data
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt| <5 Hz/s)
±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15
Hz/s)
Pickup time
f>/f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
Trip time accuracy
±1.0% of the set value or ±30 ms
4.6.1.10
Technical revision history
Table 595:
81 Technical revision history
Technical revision
Change
B
Step value changed from 0.001 to 0.0001 for the
Pickup value Freq> and Pickup value Freq< settings.
C
df/dt setting step changed from 0.005 ×Fn /s to
0.0025 ×Fn /s.
D
Internal improvement.
4.7
Impedance protection
4.7.1
Out-of-step protection 78
4.7.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Out of step protection
OOSRPSB
φ>
78
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
685