4.3.5.9
Technical data
Table 477:
87G, 87M Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±3% of the set value or ±0.002 x I
n
Trip time
1)2)
Minimum
Typical
Maximum
Low stage
36 ms
40 ms
42 ms
High stage
18 ms
22 ms
27 ms
Reset time
<40 ms
Reset ratio
Typically 0.95
Retardation time
<20 ms
1) F
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the power output contact
4.4
Unbalance protection
4.4.1
Negative-sequence overcurrent protection 46
4.4.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overcurrent
protection
NSPTOC
I2>
46
4.4.1.2
Function block
A070758-ANSI V1 EN
Figure 297:
Function block
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
587
Technical Manual