Function block
DE01
DE02
DE03
RESCMMXU1
●
●
RESVMMXU1
●
● = available in the device variant, o = optionally available in the device variant
2.3
Binary inputs
Table 3:
Explanations of the binary input table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Value
Meaning of the input states.
2.3.1
System functions
2.3.1.1
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
Table 4:
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
.Loc.stVal
Remote/Local state
0/1=Rem/Loc
2.3.1.2
LD0.LLN0 Settings supervision
Table 5:
LD0.LLN0 Settings supervision
IEC 61850 name
SA name
Description
Values
LD0.LLN0
.SetChg.stVal
-
Settings changed
1=Changed
.SetSeld.stVal
-
Settings reserved
1=Reserved
1MRS756879 D
Section 2
DNP3 data mappings
RED615
13