Table 24:
Link status
Parameter
Function
Link status
Link status in write direction: By writing 1 to the
parameter the diagnostic counters are reset to 0.
Link status in monitoring direction: If the driver is
in use by any communication protocol, the
monitoring value shows 1. In other case, the
value is 0.
8.5.1.3
Defining Ethernet port settings
1.
Select
Main menu/Configuration/Communication/Ethernet/Rear port
.
2.
Define the settings for the Ethernet port.
•
IP address
•
Subnet mask
•
Default gateway of the optional rear port Ethernet connector
8.5.1.4
Defining serial port settings
1.
Select
Main menu/Configuration/Communication/COM1
or
COM2
.
2.
Define the settings for the serial port.
It is possible to change the general serial communication parameters per port.
Select fibre or galvanic mode with the proper baud rate, parity and delays
depending on the system architecture and the selected physical
communication port.
8.5.1.5
Setting communication protocol parameters
1.
Select
Main menu/Configuration/Communication/[protocol]
.
2.
Change the protocol specific settings.
Possible settings to be changed are, for example, the selected communication
port, address and link mode.
8.5.1.6
Connecting jumper connectors
See the technical manual for details on jumper connectors.