2.3.1.88
LD0.XRGGIO130 Alarm/warning
Table 91:
LD0.XRGGIO130 Alarm/warning
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XRGGIO130
3072
192.00
.Alm.stVal
-
XRGGIO130 Alarm
1=Alarm
3073
192.01
.mcd
3074
192.02
.Wrn.stVal
-
XRGGIO130 Warning
1=Warning
3075
192.03
.mcd
2.3.2
Unmapped indications
Unmapped indications are indication data that have no initial Modbus mapping locations,
but can be added to the user-definable Modbus area using the Communication
Management tool in PCM600. If Modbus events are enabled for these indication signals,
the event identification is the user-definable area address.
2.3.2.1
All premapped three-phase protection function stages, trip/phase-
dependent objects added
Table 92:
All premapped three-phase protection function stages, trip/phase-dependent objects added
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.xxxxxxxx (various)
.Op.phsA
Phs A trip
1 = Trip
.mcd
.Op.phsB
Phs B trip
1 = Trip
.mcd
.Op.phsC
Phs C trip
1 = Trip
.mcd
2.3.2.2
Common data 2
Table 93:
Common data 2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.LDEV1
.StLstOv.stVal
Internal ind. overflow
1=Overflow
.mcd
.MeasLstOv.stVal
Internal meas. overflow
1=Overflow
Table continues on next page
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
57
Point List Manual