2.3.1.4
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 7:
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBCSWI1
POSITION
2816
176.00
.Pos.stVal.Close
Close bit
1=Close
2817
176.01
.mcd
2818
176.02
.Pos.stVal.Open
Open bit
1=Open
2819
176.03
.mcd
2820
176.04
< reserved >
2821
176.05
< reserved >
2822
176.06
.Pos.stSeld
SELECTED
CB selected for control
1=Selected
2823
176.07
.mcd
2.3.1.5
CTRL.CBXCBR1 Circuit-breaker control (1) – 52-1
Table 8:
CTRL.CBXCBR1 Circuit-breaker control (1) – 52-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.CBXCBR1
2836
177.04
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2837
177.05
.mcd
2838
177.06
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
2839
177.07
.mcd
2840
177.08
.ItlByPss.stVal
ITL_BYPASS
Interlock bypass
1=Bypass
2841
177.09
.mcd
2.3.1.6
CTRL.DCSXSWI1 Disconnector position indication (1) – 52-TOC
Table 9:
CTRL.DCSXSWI1 Disconnector position indication (1) – 52-TOC
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.DCSXSWI1
POSITION
2792
174.08
.Pos.stVal.Close
-
Close bit
1=Close
2793
174.09
.Pos.stVal.Open
-
Open bit
1=Open
2794
174.10
.Pos.stVal.Fault
-
Fault bit
1=Pos(00/11)
Section 2
1MAC252756-MB B
Modbus data mappings
22
REM615 ANSI
Point List Manual