LED
Description
7
Thermal overload of NPS protection operated
8
Disturbance recorder triggered
9
Supervision alarms
10
Arc fault detected
11
Circuit breaker failure protection operated
3.3.2.2
Default disturbance recorder settings
Table 14:
Default disturbance recorder analog channels
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
5
Uo
6
U1
7
U2
8
U3
9
U1B
10
-
11
-
12
-
Table 15:
Default disturbance recorder binary channels
Channel
ID text
Level trigger mode
1
PHIPTOC1 - start
Positive or Rising
2
DPHLPDOC1 - start
Positive or Rising
3
DPHLPDOC2 - start
Positive or Rising
4
DPHHPDOC1 - start
Positive or Rising
5
EFHPTOC1 - start
Positive or Rising
6
NSPTOC1 - start
Positive or Rising
7
NSPTOC2 - start
Positive or Rising
8
PHPTOV1 - start
Positive or Rising
9
PHPTOV2 - start
Positive or Rising
10
PHPTUV1 - start
Positive or Rising
11
PHPTUV2 - start
Positive or Rising
12
ROVPTOV1 - start
Positive or Rising
13
ROVPTOV2 - start
Positive or Rising
14
NSPTOV1 - start
Positive or Rising
Table continues on next page
Section 3
1MRS758272 B
REG615 standard configurations
40
REG615
Application Manual