2.4.2.2
LD0.VMMXU2 Three-phase voltage measurement (2)
Table 80:
LD0.VMMXU2 Three-phase voltage measurement (2)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.VMMXU2
Phase-ground voltage (2)
u16
1000
.phV.phsA.cVal.mag.f
U_DB_A
Phs A amplitude
0.00..4.00
[×Un]
u16
1000
.phV.phsB.cVal.mag.f
U_DB_B
Phs B amplitude
0.00..4.00
[×Un]
u16
1000
.phV.phsC.cVal.mag.f
U_DB_C
Phs C amplitude
0.00..4.00
[×Un]
LD0.VMMXU2
Phase-phase voltage (2)
u16
1000
.PPV.phsAB.cVal.mag.f
U_DB_AB
Phs AB amplitude
0.00..4.00
[×Un]
u16
1000
.PPV.phsBC.cVal.mag.f
U_DB_BC
Phs BC amplitude
0.00..4.00
[×Un]
u16
1000
.PPV.phsCA.cVal.mag.f
U_DB_CA
Phs CA amplitude
0.00..4.00
[×Un]
2.5
Controls
Table 81:
Explanations of the controls table columns
Column name
Description
0xA
Coil (0X) address for control value.
CS
Control structure and bit within the structure for control value.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the written value.
2.5.1
Reset, acknowledge and trigger points
Table 82:
Reset, acknowledge and trigger points
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.LLN0
2060
2.00
.IndLEDRs.Oper.ctlVal
Reset indications and LEDs
1=Reset
2061
2.01
.ProgLEDRs.Oper.ctlVal
Reset Alarm LEDs
1=Reset
DR.RDRE1
2067
2.07
.RcdTrg.Oper.ctlVal
Trig DR recording
1=Trig
Table continues on next page
Section 2
1MRS758336 B
Modbus data mappings
50
REU611
Point List Manual