8.2
Preconditions for configuration migration
The source IED configuration can be migrated to the target version using the latest
versions of PCM600 and the connectivity package.
Manual reengineering may also be required as some interface changes can exist
between the functions in different product versions.
The order code of the target IED must match the order code of the source IED.
However, the language options and product version can differ.
Table 10:
Versions supporting migration
PCM600 version
Connectivity package
version
Source version
Target version
PCM600 2.7
Ver.2.0
Ver.1.0
Ver.2.0
8.3
Backup creation
While starting IED Configuration Migration, a backup is created automatically. The
backup project is available in the PCMBackup folder under PCMdatabases. The
default location is C:\PCMdatabases\PCMBackup.
8.4
Migrating the IED configuration
Ensure that the latest connectivity package is activated in PCM600 in
Help/Update
Manager/Manage connectivity packages
. Restart PCM600 for the changes to take
place in the active connectivity package.
1.
Right-click the IED to be migrated and select
Migrate Configuration
.
Section 8
1MRS241255 B
Configuration migration
88
611 series
Engineering Manual