In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case. Therefore, the resistance of the single secondary wire can
always be used in the calculation for this kind of power systems.
25.1.5
General current transformer requirements
M11615-3 v3
The current transformer ratio is mainly selected based on power system data for
example, maximum load and/or maximum fault current. It should be verified that
the current to the protection is higher than the minimum operating value for all
faults that are to be detected with the selected CT ratio. It should also be verified
that the maximum possible fault current is within the limits of the IED.
The current error of the current transformer can limit the possibility to use a very
sensitive setting of a sensitive residual overcurrent protection. If a very sensitive
setting of this function will be used it is recommended that the current transformer
should have an accuracy class which have an current error at rated primary current
that is less than ±1% (for example, 5P). If current transformers with less accuracy
are used it is advisable to check the actual unwanted residual current during the
commissioning.
25.1.6
Rated equivalent secondary e.m.f. requirements
SEMOD53723-1 v1
M11616-3 v2
With regard to saturation of the current transformer all current transformers of high
remanence and low remanence type that fulfill the requirements on the rated
equivalent limiting secondary e.m.f. E
al
below can be used. The characteristic of
the non remanence type CT (TPZ) is not well defined as far as the phase angle
error is concerned. If no explicit recommendation is given for a specific function
we therefore recommend contacting ABB to confirm that the non remanence type
can be used.
The CT requirements for the different functions below are specified as a rated
equivalent limiting secondary e.m.f. E
al
according to the IEC 61869-2 standard.
Requirements for CTs specified according to other classes and standards are given
at the end of this section.
25.1.6.1
Busbar protection
SEMOD129059-4 v6
The CT can be of high remanence or low remanence type and they can be used
together within the same zone of protection. Each of them must have a rated
equivalent limiting secondary e.m.f. E
al
that is larger than or equal to the required
rated equivalent limiting secondary e.m.f. E
alreq
below:
The high remanence type CT must fulfill
sr
R
al
alreq
f max
ct
L
2
pr
r
I
S
E
E
0.5 I
R
R
I
I
æ
ö
³
=
×
×
×
+
+
ç
÷
è
ø
EQUATION1534 V2 EN-US
(Equation 536)
1MRK 506 369-UEN B
Section 25
Requirements
Line distance protection REL670 2.2 IEC
881
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...