![ABB REL670 2.2 IEC Applications Manual Download Page 798](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789798.webp)
t
t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 395:
BINSTATREP logical diagram
18.7.3
Setting guidelines
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
The pulse time
t
is the only setting for the Logical signal status report
(BINSTATREP). Each output can be set or reset individually, but the pulse time
will be the same for all outputs in the entire BINSTATREP function.
18.8
Fault locator LMBRFLO
IP14592-1 v2
18.8.1
Identification
M14892-1 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator
LMBRFLO
-
-
18.8.2
Application
M13752-3 v6
The main objective of line protection and monitoring IEDs is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
distance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected lines and increases the total availability of a power system.
The fault locator is started with the input CALCDIST to which trip signals
indicating in-line faults are connected, typically distance protection zone 1 and
accelerating zone or the line differential protection. The disturbance report must
also be started for the same faults since the function uses pre- and post-fault
information from the trip value recorder function (TVR).
Beside this information the function must be informed about faulted phases for
correct loop selection (phase selective outputs from differential protection, distance
protection, directional OC protection, and so on). The following loops are used for
different types of faults:
Section 18
1MRK 506 369-UEN B
Monitoring
792
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...