Func103N
: Function type number (0-255) for binary input N according to
IEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,
176: transformer differential protection and 192: line differential protection.
Info103N
: Information number (0-255) for binary input N according to
IEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
18.6.3.3
Analog input signals
M12179-92 v6
Up to 40 analog signals can be selected among internal analog and analog input
signals. PCM600 is used to configure the signals.
For retrieving remote data from LDCM module, the Disturbance
report function should be connected to a 8 ms SMAI function block
if this is the only intended use for the remote data.
The analog trigger of Disturbance report is not affected if analog input M is to be
included in the disturbance recording or not (
OperationM
=
On
/
Off
).
If
OperationM
=
Off
, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If
OperationM
=
On
, waveform (samples) will also be recorded and reported in
graph.
NomValueM
: Nominal value for input M.
OverTrigOpM
,
UnderTrigOpM
: Over or Under trig operation, Disturbance report
may trig for high/low level of analog input M (
On
) or not (
Off
).
OverTrigLeM
,
UnderTrigLeM
: Over or under trig level, Trig high/low level relative
nominal value for analog input M in percent of nominal value.
18.6.3.4
Sub-function parameters
M12179-389 v3
All functions are in operation as long as Disturbance report is in operation.
Indications
M12179-448 v4
IndicationMaN
: Indication mask for binary input N. If set (
Show
), a status change
of that particular input, will be fetched and shown in the disturbance summary on
local HMI. If not set (
Hide
), status change will not be indicated.
SetLEDN
: Set red LED on local HMI in front of the IED if binary input N changes
status.
1MRK 506 369-UEN B
Section 18
Monitoring
Line distance protection REL670 2.2 IEC
789
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...