17.13.3
Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v2
For proper operation of comparison the set value should be set within the range of
± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and
absolute values.
•
Absolute
: Comparison is performed on absolute values of input and reference
values
•
Signed
: Comparison is performed on signed values of input and reference
values.
RefSource
: This setting is used to select the reference source between input and
setting for comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when
setting
RefSource
is selected as
SetValue
.
17.13.4
Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Section 17
1MRK 506 369-UEN B
Logic
760
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...