Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 999999.9 seconds.
17.12.3
Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
The settings
tAlarm
and
tWarning
are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the
range
1.00
second ≤
tAlarm
≤
99 999.99
seconds
1.00
second ≤
tWarning
≤
99 999.99
seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit
float representation
99 999.99
seconds <
tAlarm
≤
999 999.0
seconds
99 999.99
seconds <
tWarning
≤
999 999.0
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is,
there is no check if
tAlarm
>
tWarning
.
The limit for the overflow supervision is fixed at 999999.9 seconds.
17.13
Comparator for integer inputs - INTCOMP
17.13.1
Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values
INTCOMP
Int<=>
17.13.2
Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
1MRK 506 369-UEN B
Section 17
Logic
Line distance protection REL670 2.2 IEC
759
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...