BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
STDIR
TRIP
SMPPTRC
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
FW
REV
Phase segregated trip L1, L2 and L3
from example line differential or
distance protection
Phase selection L1, L2 and L3 from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide single pole trip
To activate lockout for any trip
To reset lockout
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
OR
To prepare 3 phase trip
for any trip signal
SMBRREC
PREP3P
TR3P
STN
IEC05000545-5-en.vsdx
IEC05000545 V5 EN-US
Figure 383:
The trip logic function SMPPTRC used for single-phase tripping
application
17.1.2.3
Single-, two- or three-phase tripping
M14828-15 v5
The single-/two-/three-phase tripping mode provides single-phase tripping for
single-phase faults, two-phase tripping for two-phase faults and three-phase
tripping for three-phase faults. The operating mode is always used together with an
autoreclosing scheme with setting
ARMode
=
1/2/3 ph
or
ARMode
=
1/2 ph
.
The functionality is very similar to the single-phase scheme described above.
However, in addition to the connections for single phase SMBRREC must also be
informed that the trip is two phases by connecting the output TR2P to the input
TR2P in the SMBRREC function.
17.1.2.4
Lock-out
M14828-18 v6
The SMPPTRC function block is provided with possibilities to initiate lock-out.
The lock-out can be set to only activate the block closing output CLLKOUT or
initiate the block closing output and also maintain the trip signal output TR3P
(latched trip).
Section 17
1MRK 506 369-UEN B
Logic
744
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...