ResetTypeCrvn
: This parameter for inverse time characteristic can be set to
Instantaneous
,
Frozen time
,
Linearly decreased
. The default setting is
Instantaneous
.
tIResetn
: Reset time for step
n
if inverse time delay is used, given in s. The default
value is 25 ms.
kn
: Time multiplier for inverse time characteristic. This parameter is used for
coordination between different inverse time delayed undervoltage protections.
ACrvn
,
BCrvn
,
CCrvn
,
DCrvn
,
PCrvn
: Parameters to create a programmable under
voltage inverse time characteristic. Description of this can be found in the
Technical manual
.
CrvSatn
: Tuning parameter that is used to compensate for the undesired
discontinuity created when the denominator in the equation for the customer
programmable curve is equal to zero. For more information, see the
Technical
manual
.
IntBlkSeln
: This parameter can be set to
Off
,
Block of trip
,
Block all
. In case of a
low voltage the undervoltage function can be blocked. This function can be used to
prevent function when the protected object is switched off. If the parameter is set
Block of trip
or
Block all
unwanted trip is prevented.
IntBlkStValn
: Voltage level under which the blocking is activated set in % of
UBase
. This setting must be lower than the setting
Un<
. As switch of shall be
detected the setting can be very low, that is, about 10%.
tBlkUVn
: Time delay to block the undervoltage step
n
when the voltage level is
below
IntBlkStValn
, given in s. It is important that this delay is shorter than the
operate time delay of the undervoltage protection step.
10.2
Two step overvoltage protection OV2PTOV
IP14545-1 v3
10.2.1
Identification
M17002-1 v8
Function description
IEC 61850
identification
IEC 60617 identification
ANSI/IEEE C37.2
device number
Two step overvoltage protection
OV2PTOV
3U>
SYMBOL-C-2U-SMALLER-THAN V2 EN-US
59
Section 10
1MRK 506 369-UEN B
Voltage protection
536
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...