AngleRCA
Forward
Area
Iop = I2
Upol=-U2
Reverse
Area
IEC10000031-1-en.vsd
IEC10000031 V1 EN-US
Figure 272:
Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
UPolMin
: Minimum polarization (reference) voltage % of
UBase
.
I>Dir
: Operate residual current level for directional comparison scheme. The
setting is given in % of
IBase
. The start forward or start reverse signals can be used
in a communication scheme. The appropriate signal must be configured to the
communication scheme block.
9.6
Sensitive directional residual overcurrent and power
protection SDEPSDE
SEMOD171436-1 v4
Section 9
1MRK 506 369-UEN B
Current protection
494
Line distance protection REL670 2.2 IEC
Application manual