Figure 226:
Fault on adjacent line and its clearance causes power swinging
between sources A and C
PSLPSCH function and the basic operating principle of ZMRPSB function operate
reliably for different faults on parallel power lines with detected power swings. It
is, however, preferred to keep the distance protection function blocked in cases of
single phase-to-earth faults on so far healthy lines with detected power swings. In
these cases, it is recommended to use an optionally available directional
overcurrent earth-fault protection with scheme communication logic.
R
jX
B
A
Measured
impedance at initital
fault position
Impedance locus at initial power
swing after the fault clearance
ZMRPSB operating characteristic
Zone 2
Zone 1
IEC99000181_2_en.vsd
IEC99000181 V2 EN-US
Figure 227:
Impedance trajectory within the distance protection zones 1 and 2
during and after the fault on line B – D
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
417
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...