Figure 176:
Switchyard layout ABC_BC (3)
The interlocking functionality in 650 series can not handle the transfer bus
WA7(C).
11.5.7.2
Configuration
The signals from the other bays connected to the bus-coupler module ABC_BC are
described below.
11.5.7.3
Signals from all feeders
To derive the signals:
Signal
BBTR_OP
No busbar transfer is in progress concerning this bus-coupler.
VP_BBTR
The switch status is valid for all apparatuses involved in the busbar transfer.
EXDU_12
No transmission error from any bay connected to the WA1/WA2 busbars.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and
bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:
Signal
Q1289OPTR
189 or 289 or both are open.
VP1289TR
The switch status of 189 and 289 are valid.
EXDU_12
No transmission error from the bay that contains the above information.
Section 11
1MRK 506 334-UUS A
Control
368
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...