one wants to get the UNSUCCL (Unsuccessful closing) signal in the case the CB does not
respond to the closing command, CLOSECMD, one can set
UnsucClByCBChk
=
CB
check
and set
tUnsucCl
for instance to
1.0
s.
Priority and time tWaitForMaster
In single CB applications, one sets
Priority = None
. At sequential reclosing the function
of the first CB, for example near the busbar, is set
Priority = High
and for the second CB
Priority = Low
. The maximum waiting time,
tWaitForMaster
of the second CB is set
longer than the “auto-reclosing open time” and a margin for synchronism check at the first
CB. Typical setting is
tWaitForMaster
=
2s
.
AutoCont and tAutoContWait, Automatic continuation to the next shot if the
CB is not closed within the set time
The normal setting is
AutoCont
=
Disabled
. The
tAutoContWait
is the length of time
STBRREC (79) waits to see if the breaker is closed when
AutoCont
is set to
Enabled
.
Normally the setting can be
tAutoContWait
=
2 s
.
11.4
Apparatus control
11.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control
QCBAY
-
-
Local remote
LOCREM
-
-
Local remote control
LOCREMCTRL
-
-
11.4.2
Application
The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and grounding switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchronism check,
operator place selection and external or internal blockings.
The complete apparatus control function is not included in this product,
and the information below is included for understanding of the principle
for the use of QCBAY, LOCREM, and LOCREMCTRL for the selection
of the operator place.
1MRK 506 334-UUS A
Section 11
Control
335
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...