EQUATION288 V2 EN
(Equation 119)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
Enabled
or
Disabled
.
Pickup
: Set operate current in % of
IBase
.
IBase
is a global parameter valid for all
functions in the IED.
7.6
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC (51N/67N)
7.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step residual overcurrent
protection, zero or negative sequence
direction
EF4PTOC
2
IEC11000263 V1 EN
51N/67N
7.6.2
Application
The four step residual overcurrent protection, zero or negative sequence direction
EF4PTOC (51N_67N) is used in several applications in the power system. Some
applications are:
•
Ground-fault protection of feeders in effectively grounded distribution systems.
Normally these feeders have radial structure.
•
Back-up ground-fault protection of subtransmission and transmission lines.
•
Sensitive ground-fault protection of transmission lines. EF4PTOC (51N_67N) can
have better sensitivity to detect resistive phase-to-ground-faults compared to distance
protection.
•
Back-up ground-fault protection of power transformers with ground source at
substation.
Section 7
1MRK 506 334-UUS A
Current protection
202
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...