Table 66. Scheme communication logic for residual overcurrent protection ECPSCH
Function
Range or value
Accuracy
Scheme type
Off
Intertrip
Permissive UR
Permissive OR
Blocking
-
Communication scheme
coordination time
(0.000-60.000) s
±0.5% ±25 ms
Minimum duration of a send
signal
(0.000-60.000) s
±0.5% ±25 ms
Security timer for loss of carrier
guard detection
(0.000-60.000) s
±0.5% ±25 ms
GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1
Table 67. Local acceleration logic ZCLCPSCH
Function
Range or value
Accuracy
Operate current, LoadCurr
(1–100)% of IBase
±1.0% of I
r
Operate current, MinCurr
(1–100)% of IBase
±1.0% of I
r
Delay time on pick-up for current release
(0.000–60.000) s
±0.2% or ±35 ms whichever is greater
Delay time on drop-off for current release
(0.000–60.000) s
±0.2% or ±35 ms whichever is greater
Delay time on pick-up for MinCurr value
(0.000–60.000) s
±0.2% or ±35 ms whichever is greater
M16051-2 v11
Table 68. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Function
Range or value
Accuracy
Operate mode of WEI logic
Off
Echo
Echo & Trip
-
(5-70)% of UBase
±1.00.5% of U
r
Operate time for current reversal
logic
(0.000-60.000) s
±0.2% or ±25 ms whichever is greater
Delay time for current reversal
(0.000-60.000) s
±0.2% or ±25 ms whichever is greater
Coordination time for weak-end
infeed logic
(0.000–60.000) s
±0.2% or ±25 ms whichever is greater
Line distance protection REL650
1MRK 506 384-BEN H
Version 2.2
Hitachi Power Grids
83
© 2017 - 2021 Hitachi Power Grids. All rights reserved