Power Automation and Protection Division
I.L. 40-201.9
REL 352 Version 1.00
4-19
4
TARGET
DESCRIPTION
FORMAT
UNITS
IA
I
A
fault current magnitude
XXX.X
Amps
I
A
fault current angle
XXX.X
deg
IB
I
B
fault current magnitude
XXX.X
Amps
I
B
fault current angle
XXX.X
deg
IC
I
C
fault current magnitude
XXX.X
Amps
I
C
fault current angle
XXX.X
deg
3I0
3I
0
fault current magnitude
XXX.X
Amps
3I
0
fault current angle
XXX.X
deg
DATE
Date of fault (Month.Day)
MM.DD
YEAR
Year of fault
YYYY
TIME
Time of fault (Hours.Minutes)
HH.MM
SEC
Time of fault (Seconds)
XXXX
sec
MSEC
Time of fault (Milliseconds)
XXXX
msec
LDT1
LDT used at time of trip
XXX.X
msec
LDT2
LDT used at time of trip Term 2
XXX.X
msec
IA
∠
IB
∠
IC
∠
3I 0
∠
TABLE 4-6.
TARGET (FAULT DATA) INFORMATION
(SHEET 2 OF 2)
NOTES: The “YES/NO” targets are displayed only if they are “YES”.
The angles are not displayed if the magnitude of the value or the reference is less than 0.5 A
or 0.7 V rms.
The impedance is dependent upon the CTYP setting. The internal impedance values are for a
5 A ct. The impedance value is multiplied by 5 if a 1 A ct is used (CTYP = 1).