I.L. 40-201.9
Power Automation and Protection Division
K-4
REL 352 Version 1.00
Please note that the information applies to LP and LN as well.
IKEY
i
i
Figure 3. Square Wave Duration - 60 Hz
60 Hz
Where r = IKEY/IT [rms]
i.e. IKEY = 0.5,
IT = 5 A
IKEY time = t (r) *1000
IT computation
IT = C0xI0+C1xI1+C2xI2
Example:
Applying balanced 3-phase fault of
5A rms requires C1=1 to obtain IT
of 5A rms
I< t(r) >I
f : = 60
r:
0 0.05..1
2
⋅
,
=
t r
( )
:
1
2 f
⋅
----------
r
2
-------
asin
f
π
⋅
----------------------
=
i:
0..48
=
X
i
:
i
π
24
------
⋅
sin
=
y
i
:
i.
π
24
------
π
6
---
+
sin
=
r
t(r)•1000
0
8.33
0.05
8.15
0.1
7.96
0.15
7.77
0.2
7.58
0.25
7.39
0.3
7.2
0.35
7.01
.04
6.81
0.45
6.62
0.5
6.42
0.55
6.21
0.6
60.1
0.65
5.8
0.7
5.59
0.75
5.37
0.8
5.15
0.85
4.90
0.9
4.67
0.95
4.43
1
4.17
1.05
3.89
1.1
3.61
1.15
3.3
1.2
2.96
1.25
2.58
1.3
2.15
1.35
1.6
1.4
0.75
>>
<<[msec]