-3U
0
Operate area
3I
0
RCADir
= 0º
ROADir
= 80º
IEC06000652-3-en.vsd
IEC06000652 V3 EN
Figure 46:
Example characteristic
Non-directional earth fault current protection
Procedure
1.
Measure that the operate current is equal to the
INNonDir>
setting.
The function activates the START and STDIRIN output.
2.
Measure the operate time of the timer by injecting a current of 200% of the
operate value.
3.
Compare the result with the expected value.
The expected value depends on whether definite time
tINNonDir
or inverse time
was selected.
4.
Continue to test another function or complete the test by setting the test mode to
Off
.
Residual overvoltage release and protection
Procedure
1.
Measure that the operate voltage is equal to the
UN>
setting.
The function activates the START and STUN signals.
2.
Measure the operate time by injecting a voltage 1.2 times set
UN>
operate value.
3.
Compare the result with the set
tUN
operate value.
4.
Inject a voltage 0.8 ·
UNRel>
and a current high enough to operate the
directional function at the chosen angle.
5.
Increase the voltage until the directional function is released.
6.
Compare the measured value with the set
UNRel>
operate value.
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
158
Generator protection REG670 2.0 IEC
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...