The Denial of Service functions DOSLAN1 and DOSFRNT are included to limit the
inbound network traffic. The communication can thus never compromise the primary
functionality of the IED.
The event system has a rate limiter to reduce CPU load. The event channel has a quota
of 10 events/second after the initial 30 events/second. If the quota is exceeded the
event channel transmission is blocked until the event changes is below the quota, no
event is lost.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the fibre-optic multimode LC connector(s) (100BASE-
FX).
The IED supports SNTP and IRIG-B time synchronization methods with a time-
stamping accuracy of ±1 ms.
•
Ethernet based: SNTP and DNP3
•
With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 time synchronization methods with a time
stamping accuracy of ±5 ms.
16.2.3
Communication interfaces and protocols
Table 460:
Supported station communication interfaces and protocols
Protocol
Ethernet
Serial
100BASE-FX LC
Glass fibre (ST
connector)
EIA-485
IEC 61850–8–1
●
-
-
DNP3
●
●
●
IEC 60870-5-103
-
●
●
● = Supported
16.2.4
Settings
Table 461:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
PortSelGOOSE
Front
LAN1
-
-
LAN1
Port selection for GOOSE communication
PortSelMMS
Front
LAN1
Front+LAN1
-
-
LAN1
Port selection for MMS communication
Section 16
1MRK 502 048-UEN A
Station communication
596
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...