The BLOCKED signal is a steady signal and is set when the counter is blocked. There
are two reasons why the counter is blocked:
•
The BLOCK input is set, or
•
The binary input module, where the counter input is situated, is inoperative.
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
Note, the pulse is short, one cycle.
The SCAL_VAL signal consists of scaled value (according to parameter
Scale
), time
and status information.
15.1.8
Technical data
Table 453:
PCGGIO technical data
Function
Setting range
Accuracy
Cycle time for report of counter
value
(1–3600) s
-
15.2
Energy calculation and demand handling ETPMMTR
15.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Energy calculation and demand
handling
ETPMMTR
Wh
IEC10000169 V1 EN
-
15.2.2
Functionality
Outputs from the Measurements (CVMMXN) function can be used to calculate
energy consumption. Active as well as reactive values are calculated in import and
export direction. Values can be read or generated as pulses. Maximum demand power
values are also calculated by the function.
Section 15
1MRK 502 048-UEN A
Metering
590
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...