compensation at 5, 30 and 100% of rated current. The compensation below 5% and
above 100% is constant and linear in between, see figure
Phase currents (amplitude and angle) are available on the outputs and each amplitude
output has a corresponding supervision level output (ILx_RANG). The supervision
output signal is an integer in the interval 0-4, see section
14.1.8.4
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, amplitude and angle) are available on the
outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section
14.1.8.5
Voltage and current sequence measurements VMSQI, CMSQI
The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, other than
X_RANG, are calculated within the measuring blocks and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an integer
in the interval 0-4, see section
14.1.9
Technical data
Table 375:
CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU
Function
Range or value
Accuracy
Voltage
(0.1-1.5) ×U
r
±
0.5% of U
r
at U
£
U
r
±
0.5% of U at U > U
r
Connected current
(0.2-4.0) × I
r
±
0.5% of I
r
at I
£
I
r
±
0.5% of I at I > I
r
Active power, P
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
Reactive power, Q
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
Table continues on next page
Section 14
1MRK 502 048-UEN A
Monitoring
500
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...